Usefull OID's for APC

Afdrukken
PDF
Gebruikerswaardering: / 2
LaagsteHoogste 

APC UPS OID's from the PowerNet MiB file

Descr
 OID  Output
UPS Type .1.3.6.1.4.1.318.1.1.1.1.1.1.0  String containing UPS model, eg: Smart-UPS 1000
Battery capacity
  .1.3.6.1.4.1.318.1.1.1.2.2.1.0
  Battery capacity as % of total
Battery temperature
  .1.3.6.1.4.1.318.1.1.1.2.2.2.0
  Battery temperature in Celcius of Farenheit - depending on how UPS is configured
Battery runtime remain .1.3.6.1.4.1.318.1.1.1.2.2.3.0  Total battery runtime available based on current load
Battery replace
 .1.3.6.1.4.1.318.1.1.1.2.2.4.0
 If result = 2 then battery needs replacing (1 = ok)
Input voltage
  .1.3.6.1.4.1.318.1.1.1.3.2.1.0
  Input voltage, to the UPS device
Input frequency
  .1.3.6.1.4.1.318.1.1.1.3.2.4.0
  Input frequency in Hz
Reason for last transfer
  .1.3.6.1.4.1.318.1.1.1.3.2.5.0
  String containing reason for last transfer to battery power
1 No events
2 High line voltage
3 Brownout
4 Loss of mains power
5 Small temporary power drop
6 Large temporary power drop
7 Small spike
8 Large spike
9 UPS self test
10 Excessive input voltage fluctuation
Output voltage
 .1.3.6.1.4.1.318.1.1.1.4.2.1.0
 Output voltage from the UPS
Output frequency  .1.3.6.1.4.1.318.1.1.1.4.2.2.0  Output frequency in Hz
Output load
 .1.3.6.1.4.1.318.1.1.1.4.2.3.0
 Output load expressed as % of capacity
Output current
 .1.3.6.1.4.1.318.1.1.1.4.2.4.0
 Output current in Amps
Comms
 .1.3.6.1.4.1.318.1.1.1.8.1.0
 Whether SNMP agent is communicating with UPS device 1 = yes, 2 = no
Last Self Test result
 .1.3.6.1.4.1.318.1.1.1.7.2.3.0
 Result of last self test as text string. eg: pass or fail.
Last Self Test date
 .1.3.6.1.4.1.318.1.1.1.7.2.4.0
 Date of last self test